Tool
Panel thermal calculator
A quick first check on enclosure cooling. Enter the size, what's inside, and the temperatures. You'll see how much heat the walls can shed and whether you need a fan, a heat exchanger, or an air conditioner.
Turn on JavaScript to use the calculator.
How it works
- Surface area. Only surfaces exposed to air shed heat well. The tool uses the effective-area formulas from IEC/TR 60890, which enclosure makers also use: a wall-mounted box loses its back as a cooling surface.
- Heat through the walls. Watts = k × area × temperature difference, with typical k values: painted steel 5.5, stainless 4.5, aluminum 12, and fiberglass or plastic 3.5 W/m²K.
- Fan airflow. CFM = 3.17 × watts ÷ temperature difference in °F, at sea level. Filters cut real airflow, so pick a fan with headroom.
- Air conditioner. BTU/hr = watts × 3.412. Add margin for filters clogging and hotter days.
This is an estimate. It doesn't model direct sun, altitude, hot spots inside the panel, or blocked airflow. Have cooling sized by a qualified person before you buy equipment. We check thermal load during drawing review on panels we build.
Want us to check it?
Send the drawings and we'll check heat load as part of the review.